A collector without enough airflow overheats and throws heat back out the glazing. A collector with a huge fan and a tiny duct delivers a lukewarm breeze and a disappointed builder. This page connects three numbers: how much air you want, how big the duct has to be to carry it without a fight, and when the fan should run. It assumes you already know the heat path in how collectors work.
The wall collector used about 3 cubic feet per minute per square foot as a starting target. That is the number this sketch starts with. A thermosiphon skips the fan and therefore skips this page's fan section, not the lesson about short, generous ducts.
Difficulty
- Level
- Intermediate
- Time
- An hour of arithmetic before you buy a fan
- Skills
- Reading a fan label without believing the free-air number
Cost estimate
Free
The sketch is free. A listed fan and a listed snap disc are part of the collector budget, often a few tens of dollars if you are not hiring an electrician for a new circuit.
Materials
| Item | Qty | Notes |
|---|---|---|
| Collector area | Square feet of glazing | Not the area of the wall around it. |
| A fan whose curve you can see | 1 | Free-air cfm is the flow with no duct. You will have a duct. |
| A listed temperature control | 1 | Snap disc or a line-voltage thermostat rated for the load. Not a plastic household thermostat inside the collector. |
Airflow
Start near 2 to 4 cfm per square foot of collector. Lower in that band runs hotter and can make a weak fan look adequate. Higher moves more heat until the temperature rise gets so small the room does not feel it, and until the fan noise is the main product. Three is a middle to type into the sketch.
The number on the box is often free-air flow, measured with nothing attached. A duct, a damper, a screen absorber, and a dirty filter all add resistance. Flow falls as resistance rises. If the maker shows a curve of flow versus pressure, pick a fan that still delivers your target partway along that curve, not only at the free-air point. If there is no curve, buy a fan with free-air flow well above the target and keep the duct very short, then measure the outlet temperature and decide.
Ducts
The sketch also asks for a duct velocity. Something around 500 to 800 feet per minute is a quiet planning band for these short runs. Faster gets noisy. Slower means a duct so large it will not fit the wall. The diameter it prints is the round size that hits that velocity. Choose the next stock size you can actually buy, in metal. Keep the run to a few feet. Two elbows can matter more than a slightly small pipe.
Do not use a plastic dryer hose inside or downstream of a hot collector. It sags, it leaks, and it is not a heat-rated duct. Seal the metal joints. Insulate a duct that passes through a cold space, or you will spend the heat on the way to the room.
The damper goes in the supply, where it can fall shut. The fan can sit on the inlet so it is pushing room air in, which keeps the fan a little cooler. Either way, the fan motor does not belong in the stagnant collector.
When the fan runs
The fan should run when the collector is hotter than the room and stop when it is not. A snap disc on the absorber, set to close somewhere around 90 to 110 degrees F, is a simple version if the disc is listed for the way you wire it. A differential control that compares collector and room is kinder and costs more. Either one must fail toward off. A fan that runs all night pulls room air through a cold box if the damper also fails.
Do not put the control inside the collector unless it is rated for that temperature. Household thermostats are not.
Compute a target flow
Area times about 3 cfm per square foot. Write the number down.
Size a short metal duct
Use the velocity sketch. Avoid crushed bends and plastic hose.
Pick a fan for the duct, not for the box label
Free-air flow is the optimistic end. Leave margin.
Control it from collector temperature
Listed snap disc or a differential control. Off at night. Test that off.
Further reading
These links go to outside sources. This book cites them by link and does not copy their words or pictures.
- https://www.builditsolar.com/Projects/SpaceHeating/Space_Heating.htm
- https://www.builditsolar.com/Projects/SpaceHeating/SolAirCol/SolAirCol.htm
- https://www.builditsolar.com/Experimental/PopCanVsScreen/PopCanVsScreen.htm
- https://www.builditsolar.com/Experimental/AirColTesting/Index.htm
- https://www.builditsolar.com/Experimental/AirColTesting/FlowTesting.htm
- https://www.builditsolar.com/Experimental/ScreenAbsorber/ScreenAbsorber.htm
- https://www.builditsolar.com/Experimental/WindowCollector/OverWindowCollector.htm
- https://www.builditsolar.com/Projects/SpaceHeating/KenSoffitCollector/Main.htm
- https://www.builditsolar.com/Projects/SpaceHeating/360SFAir/360SFAir.htm
General education, not a permit or a stamped design. Follow the safety note in the guide, read the safety disclaimer, and hire a licensed trade when the work requires one.